Note: Claims are shown in the official language in which they were submitted.
CLAIMS:
1. A system of in-floor ducting, located above a concrete slab, between
sleepers
and below a raised floor, to circulate air and regulate room temperature,
where at
least some of the air is moved through a channel that is recessed into the top
of
the concrete slab, said air then moves up out of said channel into plenums
formed between the concrete slab, at least two sleepers and a raised floor,
said
air then moves through plenums above the concrete slab and under the raised
floor, said air then allowed to escape through holes in raised floor and
return to
room.
2. The combination defined in Claim 1 where the sleepers are oriented
substantially
perpendicular to the channel in the concrete slab.
3. The combination defined in Claim 1 where the air is supplied to the channel
in
the concrete slab by an intersecting vertical air duct.
4. The combination defined in Claim 1 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
for support in areas where the ground freezes in the winter.
5. The combination defined in Claim 1 where the concrete slab is part of an
upper
floor of a building.
6. A system of in-floor ducting, located above a concrete slab, between
sleepers
and below a raised floor, to circulate air and regulate room temperature,
where
substantially all of the air is moved through a channel that is recessed into
the
top of the concrete slab, said air then moves up out of said channel into
plenums
formed between the concrete slab, at least two sleepers and a raised floor,
said
air then moves through plenums above the concrete slab and under the raised
floor, said air then is gathered into another air duct for delivery to desired
room or
rooms in the building.
7. The combination defined in Claim 6 where the sleepers are oriented
substantially
5A
perpendicular to the channel in the concrete slab.
8. The combination defined in Claim 6 where the air is supplied to the channel
in
the concrete slab by an intersecting vertical air duct.
9. The combination defined in Claim 6 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
for support in areas where the ground freezes in the winter.
10. The combination defined in Claim 6 where the concrete slab is part of an
upper
floor of a building.
11. A system of in-floor ducting, located above a concrete slab, between
sleepers
and below a raised floor, to circulate air and regulate room temperature,
where
substantially all of the air is moved through a furnace, heat-exchanger, air-
conditioner, etc. commonly used in the Heating, Ventilation, and Air
Conditioning
(HVAC) industry, said air is then moved through a channel that is recessed
into
the top of the concrete slab, said air then moves up out of said channel into
plenums formed between the concrete slab, at least two sleepers and a raised
floor, said air then moves through plenums above the concrete slab and under
the raised floor, said air then is gathered into another air duct for delivery
to
desired room or rooms in the building.
12. The combination defined in Claim 11 where the sleepers are oriented
substantially perpendicular to the channel in the concrete slab.
13. The combination defined in Claim 11 where the air is supplied to the
channel in
the concrete slab by an intersecting vertical air duct.
14. The combination defined in Claim 11 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
for support in areas where the ground freezes in the winter. The combination
defined in Claim 1 where the concrete slab is part of an upper floor of a
building.
15. The combination defined in Claim 11 where the concrete slab is part of an
upper
floor of a building.
16. A system of in-floor ducting, located above a concrete slab, between
sleepers
6
and below a raised floor, to circulate air and regulate room temperature,
where at
least some of the air is moved through a channel that is located on top of the
concrete slab, said air then moves through the channel and into plenums formed
between the concrete slab, at least two sleepers and a raised floor, said air
then
moves through plenums above the concrete slab and under the raised floor, said
air then allowed to escape through holes in raised floor and return to room.
17. The combination defined in Claim 16 where the sleepers are oriented
substantially perpendicular to the channel in the concrete slab.
18. The combination defined in Claim 16 where the air is supplied to the
channel in
the concrete slab by an intersecting vertical air duct.
19. The combination defined in Claim 16 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
for support in areas where the ground freezes in the winter.
20. The combination defined in Claim 16 where the concrete slab is part of an
upper
floor of a building.
21. A system of in-floor ducting, located above a concrete slab, between
sleepers
and below a raised floor, to circulate air and regulate room temperature,
where
substantially all of the air is moved through a channel that is located on top
of the
concrete slab, said air then moves out of said channel into plenums formed
between the concrete slab, at least two sleepers and a raised floor, said air
then
moves through plenums above the concrete slab and under the raised floor, said
air then is gathered into another air duct for delivery to desired room or
rooms in
the building.
22. The combination defined in Claim 17 where the sleepers are oriented
substantially perpendicular to the channel in the concrete slab.
23. The combination defined in Claim 17 where the air is supplied to the
channel in
the concrete slab by an intersecting vertical air duct.
24. The combination defined in Claim 17 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
7
for support in areas where the ground freezes in the winter.
25. A system of in-floor ducting, located above a concrete slab, between
sleepers
and below a raised floor, to circulate air and regulate room temperature,
where
substantially all of the air is moved through a furnace, heat-exchanger, air-
conditioner, etc. commonly used in the Heating, Ventilation, and Air
Conditioning
(HVAC) industry, said air is then moved through a channel that is recessed
into
the top of the concrete slab, said air then moves up out of said channel into
plenums formed between the concrete slab, at least two sleepers and a raised
floor, said air then moves through plenums above the concrete slab and under
the raised floor, said air then is gathered into another air duct for delivery
to
desired room or rooms in the building.
26. The combination defined in Claim 25 where the sleepers are oriented
substantially perpendicular to the channel in the concrete slab.
27. The combination defined in Claim 25 where the air is supplied to the
channel in
the concrete slab by an intersecting vertical air duct.
28. The combination defined in Claim 25 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
for support in areas where the ground freezes in the winter.
29. The combination defined in Claim 25 where the concrete slab is part of an
upper
floor of a building.
30. A system of in-floor ducting, located above a concrete slab, between
sleepers
and below a raised floor, to circulate air and regulate room temperature,
where
substantially all of the air is moved through a furnace, heat-exchanger, air-
conditioner, etc. commonly used in the Heating, Ventilation, and Air
Conditioning
(HVAC) industry, said air is then moved through a channel that is located on
the
top of the concrete slab, said air then moves out of said channel into plenums
formed between the concrete slab, at least two sleepers and a raised floor,
said
air then moves through plenums above the concrete slab and under the raised
floor, said air then is gathered into another air duct for delivery to desired
room or
rooms in the building.
8
31. The combination defined in Claim 30 where the sleepers are oriented
substantially perpendicular to the channel in the concrete slab.
32. The combination defined in Claim 30 where the air is supplied to the
channel in
the concrete slab by an intersecting vertical air duct.
33. The combination defined in Claim 30 where the concrete slab is part of a
Frost
Protected Shallow Foundation system, where the concrete slab is properly
designed and insulated and the building does not require piles and grade beams
for support in areas where the ground freezes in the winter.
34. The combination defined in Claim 30 where the concrete slab is part of an
upper
floor of a building.
9